application of the static mixer on desuperheater performance
کد مقاله : 1155-FDC
نویسندگان
Mohammad Saadatbakhsh *1، Fallah Mahmoudi Surman Abad2، Hooman Nowroozlou2، Kasra Habibi3
1عضو هیات علمی
2دانشجو کارشناسی ارشد تبدیل انرژی
3دانشجوی کارشناسی
چکیده مقاله
One of the methods to decrease the temperature of superheated steam is by injecting cooling water using a desuperheater, the evaporation of the droplets leads to a reduction in superheated steam’s temperature. In this study, a desuperheater model with the injection of cooling water against the direction of the superheated steam flow after a static mixing element and another model without the static mixer are simulated by using the discrete phase model (DPM) and implementing the lagrangian-eulerian approach. Heat and mass transfer between water droplets and superheated steam is simulated as a two-phase 3D flow in ANSYS FLUENT by considering the standard k-ε turbulence model. The effect of the static mixer on droplet evaporation is studied, the results indicate that the presence of a static mixer leads to an increase in mixture between the injected droplets and superheated steam and this phenomenon improves the heat transfer and increases the evaporation rate
کلیدواژه ها
Desuperheater- Structural innovation- Numerical simulation- DPM- Thermal desalination
وضعیت: پذیرفته شده برای ارسال فایل های ارائه پوستر